What an OT/ICS pentest report must contain

An OT/ICS pentest report carries obligations IT reports do not. This is what every section must include to stand up under regulatory scrutiny.

Joel Aviad OssiJoel Aviad OssiRed Team Lead, RedTeam Security
8 min read
An isometric arrangement of a thick report binder, stacked grid chart pages, and a sealed evidence envelope on an industrial desk, connected by fine amber circuit-trace lines against a deep charcoal background.

Key takeaways

  • The executive summary must carry the report classification level and distribution list. UAE regulatory submissions expect an evidence pack with defined recipients.
  • Findings must be mapped to IEC 62443 zones and conduits so the remediation owner can act without re-reading the technical appendices.
  • A remediation matrix that shows patch availability and remediation category gives the operations team a prioritised list they can execute within scheduled maintenance windows.
  • Verification on live OT equipment requires a maintenance window, safety interlock documentation, and a rollback plan before any fix can be confirmed as closed.
  • NESA CIIP obligations apply to OT operators of critical infrastructure, and the report evidence pack must be structured to support an Information Assurance Report submission.

The executive summary and its distribution obligations

The executive summary is the page a board member reads and the section a regulator opens first. It states what was tested, the overall risk posture across the tested zones, and the three to five findings with the highest operational consequence. Write it to one page. Every other decision about depth, format, and sequencing follows from whether this page is clear.

Before any finding is listed, the summary must carry the report classification level and its distribution list. A typical OT/ICS pentest report is marked CONFIDENTIAL and distributed to the asset owner, the OT team lead, the CISO, and any regulator named in the engagement letter. In the UAE, DESC and NESA expect evidence packs with defined recipient sets when a submission accompanies an assurance review. Listing the distribution on the first page is not a formality: it sets the legal and regulatory status of the document from the moment it leaves the engagement team.

Where the engagement covers infrastructure under a national critical information infrastructure protection regime, the summary should confirm whether a regulatory submission is planned, who will carry it, and which evidence appendices support it. The CISO reading this section needs to know whether the document in their hands is the evidence pack they file with a regulator or the working document they hand to the remediation team. Both are legitimate purposes; they require different handling.

The six sections every OT/ICS pentest report carries, in the order a reader and a regulator encounter them.

Scope, zones, and the testing constraints the report inherits

The scope section records what was tested and, equally, what was not. List every asset by tag and IP address, the network zone it belongs to, the protocols in scope, and the safety constraints applied during the engagement. An OT test almost always excludes write operations to certain registers, specific times of day, and PLCs that have no warm standby. Those exclusions belong here, stated precisely, so a reader who later finds an untested path cannot assume it was within scope.

The methodology block names the standard the work was conducted against. NIST SP 800-82 is the primary guide for industrial control system security assessment; state the revision in use. Agreeing depth, protocol coverage, and zone access before day one is the subject of how to buy an OT/ICS pentest; what this section records must match what the proposal agreed. A discrepancy between contracted scope and reported scope is a gap a technical auditor will note.

State the testing window with its rationale. An engagement run during a scheduled maintenance window with production halted carries a different risk profile than one run against live equipment with a safety observer on standby. State which it was, who the named safety contacts were, and what the emergency stop procedure was. The operations team inheriting this report needs to understand how the test was conducted before they can plan a remediation sequence.

Vulnerability findings and the IEC 62443 classification

Each finding must stand alone. A finding that requires the reader to cross-reference three other sections to understand what it means will not be acted on. State the affected asset, the vulnerability class, the attack path, the potential consequence in operational terms (loss of view, loss of control, unsafe state), and the evidence. A file name is not evidence. The capture itself, the reproduction steps, and the affected register or function code are evidence.

Map every finding to an IEC 62443 zone and conduit. IEC 62443 organises an industrial control system into zones of differing trust, connected by conduits, and assigns a security level target to each zone based on the consequence of a compromise. A finding in Zone 2 (a process cell) that crosses the conduit to Zone 3 (the SCADA network) has a different remediation scope and regulatory weight than one contained within a single zone. Without this mapping the operations team cannot identify which compensating controls apply, and the remediation owner cannot scope the fix without re-reading the appendices. The table below shows a structured finding format using the IEC 62443 zone model.

CVSS scoring applies to OT findings, but the base score alone is not sufficient. An unauthenticated write to an output register may score 9.1 under the FIRST CVSS framework, but the operational consequence depends on whether the process is safety-critical. Annotate each finding with the operational consequence class: loss of view, loss of control, loss of safety, or manipulation of view. MITRE ATT&CK for ICS provides the tactic and technique classification that makes this annotation systematic. The Modbus/TCP unauthenticated command injection article shows how a technique-level description changes the priority a finding receives in a real OT environment.

Structured finding format mapping each vulnerability to its IEC 62443 zone, security level gap, and operational consequence.
FieldExample value
TitleUnauthenticated write to output coils via Modbus/TCP
Affected assetPLC-04, process cell Zone 2
IEC 62443 zone/conduitZone 2, conduit to Zone 3 SCADA network
Security level gapSL-T 2, SL-A 0
CVSS v3.19.1 (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:H)
Operational consequenceLoss of control
RemediationAuthenticated Modbus gateway or firewall rule
EvidenceAppendix C, captures 001 to 003

The risk and remediation matrix

A remediation matrix gives the operations team a decision tool, not a to-do list. Plot findings on two axes: operational risk (what breaks if exploited, and at what speed) and remediation effort (calendar time to deploy a confirmed fix, not engineer hours). A finding with a patch available and a deployment path through the next maintenance window sits in a different cell than one requiring a firewall policy change agreed across three operational and network teams. The matrix makes that distinction visible before any work is scheduled, and it is the section an operations manager and a CISO will look at before any other.

Label each finding's remediation category explicitly: patch available, configuration change, compensating control, or architecture change. Each category has a different owner and a different approval path inside an OT environment. A configuration change to a PLC parameter is an engineering change request with its own safety review. A compensating control that adds a firewall rule between zones is a network change requiring network team sign-off. An architecture change that reroutes a conduit is a project with a capital budget and a shutdown window. These ownership boundaries must be visible in the report, because an OT change cycle runs to weeks or months, not the hours of a server patch.

Plotting OT findings by operational risk against remediation effort reveals which fixes belong in the next window and which need a funded project.

Verifying fixes on live OT equipment

The retest section of an OT report carries different weight than its equivalent in an IT assessment. Confirming that a PLC firmware update was applied, that a firewall rule is in place between zones, or that an authentication requirement is enforced cannot be done on an ad hoc basis. Every fix must be verified inside a scheduled maintenance window, with the safety interlock state documented before and after the change. The verification record is not optional: it is the evidence that a finding is closed.

For each finding, the report must specify the verification procedure. A finding patched at firmware level is verified by reading the version string and confirming the vulnerable function code is no longer reachable. A finding addressed by a firewall rule is verified by replaying the same traffic and confirming the rule drops it. A compensating control limiting register access is verified by confirming which function codes are refused. Vague retest records stating confirmed fixed without supporting evidence do not satisfy a technical reviewer. The article on engineering workstation to PLC logic tampering illustrates why verification at the PLC level requires equipment-specific procedures.

Where a fix cannot be tested on live equipment before the next major maintenance window, state that explicitly in the report. Record the expected verification date and note which compensating controls are in place in the interim. An open finding with a verified compensating control and a committed verification date is a managed risk. An open finding with no stated path to verification is not. CISA guidance on industrial control system security describes the interim-control expectation in the context of critical infrastructure protection, and it aligns with what NESA and DESC reviewers look for when they open an evidence pack.

Technical appendices and evidence packaging

The appendices are the raw evidence that makes every finding reproducible. A finding that cannot be reproduced is not a finding. Each appendix should be indexed by finding number and contain the original network capture or screenshot, the commands run and their output, the firmware version string confirming the affected build, and the timestamp of the test. Where a tester used a constructed environment to demonstrate a risk, label it. Where the finding was demonstrated on live equipment, state the safety precautions taken during that demonstration.

Package the appendices with the same classification as the report body. A full packet capture of a process network is sensitive data: it reveals asset inventory, protocol configuration, and register maps that are directly useful to an attacker with network access to the environment. In an infrastructure pentest context an appendix is typically shared with the operations team and deleted after remediation; in an OT report the retention and destruction schedule belongs in the document itself. State it on the cover page and confirm it in the engagement letter. What your team can observe during a test, as detailed in what your OT monitoring should catch during an ICS pentest, is only actionable if the evidence the appendix preserves is complete.

OT/ICS pentest reports in the UAE regulatory context

In the UAE, the obligations attached to an OT/ICS pentest report depend on which sector the asset owner operates in. NESA governs critical information infrastructure and publishes the UAE Information Assurance Regulation, which requires operators to conduct and document security assessments. NESA's Critical Information Infrastructure Protection (CIIP) framework specifically addresses OT and SCADA environments, and a pentest report submitted as assurance evidence must be structured to support an Information Assurance Report. Without a classification level, a distribution list, and a finding-level evidence pack, the document does not satisfy what NESA expects from a CIIP submission.

Dubai entities that supply services to government or manage critical systems fall under DESC, the Dubai Electronic Security Centre, which issues its own information assurance standards. DESC expects structured security testing evidence, and a report that names findings without supporting evidence appendices does not meet the submission bar. Abu Dhabi healthcare operators are bound by ADHICS, administered by the Department of Health, which requires documented security testing of connected operational systems. The Central Bank of the UAE framework applies to financial institutions operating OT-adjacent infrastructure, such as payment processing systems with physical control components.

For an OT pentest engagement covering infrastructure with cross-emirate reach, the report may need to satisfy both Abu Dhabi and Dubai regulatory submissions simultaneously. The classification and distribution structure agreed at the start of the engagement, and documented in the executive summary, is what makes that possible. A single well-structured report can serve as both the CISO's working document and the regulator's evidence pack. The federal baseline is the UAE Information Assurance Regulation, available from the TDRA, which both emirate-level frameworks build on.

Frequently asked questions

What does an OT/ICS pentest report contain?

An OT/ICS pentest report contains six sections: an executive summary with classification and distribution list, a scope and methodology section, vulnerability findings mapped to IEC 62443 zones, a remediation matrix, a retest record, and technical appendices. The findings section maps each vulnerability to an affected zone, a security level gap, a CVSS score, and an operational consequence class. Each section has a different primary audience and must stand alone.

How does an OT/ICS pentest report differ from an IT penetration test report?

An OT/ICS pentest report differs in three main ways. Findings are mapped to IEC 62443 zones and security levels rather than CVSS alone, because the remediation owner needs to know which part of the control system is affected. The remediation matrix must account for maintenance windows and safety interlocks, because fixes cannot be deployed on an ad hoc basis. The retest record must specify the exact verification procedure for each finding, because confirming a fix on live OT equipment requires a scheduled window with documented safety precautions.

What is IEC 62443 and why does it appear in an OT/ICS pentest report?

IEC 62443 is the international standard series for industrial automation and control system security. It defines a zone and conduit model that divides a control system into areas of differing trust, and assigns security level targets to each zone based on the consequence of a compromise. A pentest report maps each finding to this model so the remediation owner can identify which zone boundary a fix must address, rather than treating every finding as a generic network problem with a single owner.

What report classification should an OT/ICS pentest report carry?

Most OT/ICS pentest reports are classified CONFIDENTIAL, with distribution limited to the asset owner, the OT team lead, the CISO, and any regulator named in the engagement letter. The classification level and distribution list must appear in the executive summary. In the UAE, regulatory submissions to NESA or DESC require a defined distribution structure, and a report without one cannot be used directly as an evidence pack for an assurance submission.

How is retesting handled in an OT/ICS environment?

Retesting in an OT environment must happen inside a scheduled maintenance window, with safety interlock states documented before and after any change. Each finding requires a specific verification procedure: reading a firmware version string, replaying original traffic to confirm a firewall rule blocks it, or confirming which function codes are refused after a register access control is applied. Where a fix cannot be verified before the next maintenance window, the report records the expected verification date and the compensating controls in place in the interim.

What does NESA require from an OT security assessment report?

NESA requires operators of critical information infrastructure to conduct and document security assessments under the UAE Information Assurance Regulation and the CIIP framework. A pentest report submitted as assurance evidence must carry a classification level, a distribution list, finding-level evidence, and a retest record. Without these, the document does not satisfy the structure NESA expects for an Information Assurance Report covering OT or SCADA environments.

What evidence appendices should an OT/ICS pentest report include?

Evidence appendices should be indexed by finding number and contain the original network capture or screenshot, the commands run and their output, the firmware version string confirming the affected build, and the timestamp of the test. The appendices should carry the same classification as the report body, with a stated retention and destruction schedule. A packet capture of a process network reveals asset inventory and register maps, so its handling requires the same care as the report itself.

How do you prioritise findings in an OT/ICS pentest report?

Findings are prioritised on a remediation matrix with two axes: operational risk (what breaks if exploited, and at what speed) and remediation effort (calendar time to deploy a fix). The matrix also shows the remediation category for each finding: patch available, configuration change, compensating control, or architecture change. Each category has a different owner and approval path, so the matrix gives the operations team and change management a clear starting point.

What is a security level gap in IEC 62443 terms?

A security level gap in IEC 62443 terms is the difference between the security level target assigned to a zone (what it is designed to resist) and the security level achieved (what the test found it actually resists). A gap of SL-T 2 against SL-A 0 means the zone is designed to resist a motivated attacker with moderate resources but currently offers no resistance at all. This gap drives the finding's priority in the remediation matrix.

What should the executive summary of an OT/ICS pentest report include?

The executive summary should state what was tested, the overall risk posture across the tested zones, and the three to five findings with the highest operational consequence. It must also carry the report classification level and its distribution list, so that regulatory and legal obligations are clear from the first page. For engagements covering critical infrastructure, it should confirm whether a regulatory submission is planned and who will carry it.

The engagements this applies to

Joel Aviad Ossi, Red Team Lead at RedTeam Security
Joel Aviad OssiRed Team Lead, RedTeam Security

Joel Aviad Ossi is Red Team Lead at RedTeam Security, the Dubai-licensed trading brand of WebSec FZCO. He scopes and runs objective-based engagements across the UAE.

Let's talk about your security

Tell us the objective you want tested. We will come back with a scope, a timeline and a quote, under NDA from the first conversation.

Email [email protected]
IFZA Business Park, Building A2
Nadd Hessa, Dubai Silicon Oasis
Dubai, United Arab Emirates